Fire fighting units according to EN12845 - UNI10779 norms with vertical pumps and external engine

  • Vertical-Turbine-VTS---Fire-Fighting-Units|VTS-P2M---FIRE-FIGHTING-UNIT|Fire-fighting-units-according-to-EN12845---UNI10779-norms-with-vertical-pumps-and-external-engine
  • Vertical-Turbine-VTS---Fire-Fighting-Units|VTS-P2M---FIRE-FIGHTING-UNIT|Fire-fighting-units-according-to-EN12845---UNI10779-norms-with-vertical-pumps-and-external-engine

NR.1 MAIN DIESEL MOTORPUMP + NR.1 BACKUP DIESEL MOTOR PUMP + JOCKEY PUMP

vts_p2m.JPGComponent list

1. Service vertical pump
1A. Backup vertical pump
2. Shaft line for service and backup pump
3. Drive unit to link the pumps and diesel engine
4. Diesel engine for service pump and backup pump
5. Submersible jockey pump
6. Swing Check Valve ("Clapet" Valve)
7. Shut-off valve lockable
8. Check valve
9. Ball valve with level
10. Reversible delivery manifold with blind flange
11. Shunt for flow meter
12. Predisposition for sprinkler kit
13. Starting kit for main pump composed by 2 pressure  switch 2-14 bar with integrated test button,
1 pressure gauge 0-16 bar and by-pass circuit
14. Starting kit for jockey electric pump composed by
1pressure switch with integrated test button,
1 pressure gauge
15. Electrical control panels (one for each pump)
16. Kit recycling diaphragm complete with visual flow indicator
17. Pressure gauge 0-16 bar
18. Diaphragm pressure vessel 24LT PN16
19. Rubber strain neutralizer
20. biflanged 90° curve
21. Fuel tank for diesel engine
22. Rubber anti-vibration joints
23. Frame

Datasheet